UPS Supply for Primary Data Centre
Tender ID: 569053
Tender Details
Tender Description
The University of Canterbury (UC) Primary Data Centre (PDC) has an Uninterruptable Power Supply (UPS) that is at the end of life and needs to be replaced.
• 2N configuration with 50kW current load and at least 25% immediate growth with preference for 100 to 200% growth available but not installed. Each UPS/battery chain to support entire load so perhaps 150KVa
• Minimum runtime at 50kW of 15 minutes on single UPS (30+ on dual). Would also be good to have a 45-minute single UPS option
• Both UPS and battery replacement.
• E-waste Disposal of 4 x 200kva old units (UC will dispose of the current batteries)
• Installation and commissioning
All of the infrastructure is present for housing, monitoring and connecting and bypassing the battery banks. So basically, just swapping out UPS and batteries and commissioning.
• Please provide whole of life costs including detail of the recommended servicing cost, frequency, and duration of servicing.